FA-300 Series LCD Version Installation and Operation Manual
51
8. i
3
Loop Test (Command-Menu)
The i
3
maintenance test is designed to test the devices on the i
3
zone. If there is noise on the line or if the device is
too far away from the panel, the devices may not respond to the panel inquiries. An i
3
maintenance test can be
invoked from the command menu. If the fire alarm has just been powered up or reset, wait six minutes before
selecting the i
3
loop test. If the i
3
loop test is selected, the following message appears on the screen:
If you select “yes” by pressing “ENTER”, the display will ask you for which zone you want to perform the i
3
test. Note
that only one zone at a time can be in maintenance test. Select the zone by pressing the “UP” and “DOWN” keys
and then pressing the “RIGHT” key to select the device. After the device is selected press “ENTER”.
If the i
3
maintenance test is selected within six minutes after power-up or reset, the following information message
is displayed.
If a zone is selected that is not configured as an i
3
zone, the following message is displayed:
Once the zone goes into the i
3
loop test, no other zone can be put into the test. The maintenance test will take five
minutes. During this time you can walk through the device and make sure all the devices are working properly. The
following table lists the status of the devices while in loop test.
You can cancel the maintenance test either by pressing the “RESET” key or by going into the configuration section
and canceling the test.
Note: Refer to How to Use the Keypad to Program the FA-300 on page 39 for detailed instructions on
making menu selections.
Note: Out of sensitivity can mean the device is dirty.
i
3
Detector Condition
Green LED Red LED
Proper operation Double blink every 5 sec OFF
Out of sensitivity OFF Double blink every 5 sec
Freeze condition OFF Double blink every10 sec
Perform the i3
Loop test? Y
-I3 TEST ZONES-
[ ]Zone-1
The selected zone
is not ready yet
The selected zone
is not i3 type