Introduction2IntroductionMircom's FA-300 Series Fire Alarm Control Panel is a Digital Signal Processor (DSP) based fire panel. The FA-300 provide
FA-300 Series LCD Version Installation and Operation Manual3ConventionsCircuitsRefers to an actual electrical interface for Initiating (Detection) and
System Components4System ComponentsMain Fire Control PanelModel DescriptionFA-301-12DDRTwelve-Zone Fire Alarm Control Panel with LCD display and diale
FA-300 Series LCD Version Installation and Operation Manual5Relay Module: 12 RelaysRelay Modules: Six RelaysPolarity reversal/city tieModel Descriptio
System Components6Remote AnnunciatorSmart Relay ModuleInput Class A converter: Six CircuitsModel DescriptionRAM-300LCDRRemote Annunciator Module, LCD
FA-300 Series LCD Version Installation and Operation Manual7Output Class A converter: four circuitsOutput Class A converter: two circuitsActive end-of
Mechanical Installation8Mechanical InstallationInstalling the EnclosureInstall the FA-300 Series Fire Alarm Panel enclosure as shown below for the twe
FA-300 Series LCD Version Installation and Operation Manual9Figure 2: FA-301-12DDR Box dimensions, semi-flush mounting with trim ringThe figure below
Mechanical Installation10Figure 2A: FA-300-6DDR/6DR Box dimensions, mounting and trim ring17"22.5"Adhere trim ring towall surface aroundthe
FA-300 Series LCD Version Installation and Operation Manual11Installing the Adder ModulesFA-300 Series Fire Alarm panels come pre-assembled with all c
Copyrights and TrademarksThis manual is copyright 1994 - 2006 by Mircom Technologies Limited.No part of this publication may be reproduced, transmitte
Mechanical Installation12Figure 4: Installation of Adder Modules for FA-300 LCD PanelsBATTERY BATTERYCLASS-A converter board for detection circuits IC
FA-300 Series LCD Version Installation and Operation Manual13DIP Switch and Jumper Selections for Main Board and Adder Modules Main Fire Alarm BoardFi
DIP Switch and Jumper Selections for Main Board and Adder Modules 14Figure 6: Main Fire Alarm Board DIP switch and jumper settings for FA-300 LCD Pane
FA-300 Series LCD Version Installation and Operation Manual15ICAC-306 Input Class-A Converter Adder ModuleFigure 7: ICAC-306 Input Class-A Converter A
DIP Switch and Jumper Selections for Main Board and Adder Modules 16OCAC-304/302 Output Class-A Converter Adder ModuleFigure 8: OCAC-304/302 Output Cl
FA-300 Series LCD Version Installation and Operation Manual17Programming the relaysA typical relay circuit is shown below in Figure 8 with the jumper
DIP Switch and Jumper Selections for Main Board and Adder Modules 18Polarity Reversal and City Tie Module (Model PR-300) Figure 12: Polarity reversal
FA-300 Series LCD Version Installation and Operation Manual19Field wiringMain Fire Alarm Board Field WiringWire devices to the terminals as shown in t
Field wiring20Figure 14: Initiating circuit– Class A or Style D wiringIndicating Circuit WiringThe FA-300 Series Fire Alarm supports Class B (Style Y)
FA-300 Series LCD Version Installation and Operation Manual21Figure 16: Indicating circuit – Class A or Style Z wiringFour Wire Smoke Detector WiringF
Cautions and WarningsREAD AND SAVE THESE INSTRUCTIONS. Follow the instructions in this installation manual. These instructions must be followed to avo
Field wiring22Dialer Wiring If you have Fire Alarm Panel Models FA-301-12DDR or FA-300-6DDR there is a dialer on board and terminals marked Line 1 and
FA-300 Series LCD Version Installation and Operation Manual23Relay Adder Module Wiring Wire relays on the relay adder modules RM-312 and RM-306 as sho
Field wiring24Polarity Reversal and City Tie Module (PR-300) WiringWire PR-300 Polarity Reversal and City Tie Module (if used) as shown in Figure 19,
FA-300 Series LCD Version Installation and Operation Manual25Figure 22: Power supply connectionWiring Tables and Information Table 3: Initiating Circu
Field wiring26Table 4: Indicating Circuit WiringFour-Wire Smoke Power (regulated)4-wire smoke power is provided for 4-wire smoke detectors. This filte
FA-300 Series LCD Version Installation and Operation Manual27System CheckoutBefore turning the power “ON”To prevent sparking, do not connect the batte
Indicators, Controls and Operations28Indicators, Controls and OperationsRefer to Figure 21 below which shows the LCD Display, the Keypad and Control B
FA-300 Series LCD Version Installation and Operation Manual29Common IndicatorsBuzzerThe Buzzer is activated by any of the following events:If the Buzz
Indicators, Controls and Operations30Signal Silence ButtonActivation of the Signal Silence button when the panel is in alarm deactivates any Silenceab
FA-300 Series LCD Version Installation and Operation Manual31Circuit TypesInitiating (Detection) Circuit TypesNon-Verified AlarmA Non-Verified alarm i
Indicators, Controls and Operations32either manually or automatically. While sounding, these devices follow the pattern appropriate for the condition:
FA-300 Series LCD Version Installation and Operation Manual33Fire Alarm OperationIn a basic system set up all alarm inputs are treated in a similar ma
Supported Protocols/Devices34Supported Protocols/DevicesSynchronous StrobesThe synchronous strobe models that are supported by the FA-300 panel includ
FA-300 Series LCD Version Installation and Operation Manual35Open circuit troubleIf the loop is broken the panel shows open loop trouble. The panel ca
Configuration 36Configuration There are three methods of configuring the FA-300 LCD Series Fire Alarm Panels:Direct configuration using the main LCD d
FA-300 Series LCD Version Installation and Operation Manual37Command MenuThe main command menu is pictured below. The first line of the LCD will alway
Configuration 381. FA-300 CONFIG (Command-Menu)The following is a detailed description of the FA-300 configuration menu.Command Menu/FA-300 Config--&g
FA-300 Series LCD Version Installation and Operation Manual39How to Use the Keypad to Program the FA-3001. Press MENU to enter the command menu.2. Sel
Configuration 40Command Menu/FA-300 Config/Features/6.Signal-Silence Inhibit timer[X] DISABLE->Default[ ] 10 SEC [ ] 20 SEC [ ] 30 SEC[ ] 1 MINUse
FA-300 Series LCD Version Installation and Operation Manual41Command Menu/FA-300 Config/Features/13.Signal Isolators[ ] ENABLE [X] DISABLE ->DefEna
FA-300 Series LCD Version Installation and Operation ManualiContentsIndustry Canada and FCC Notice ...
Configuration 42Command Menu-->FA-300 ConfigInp ZoneThis menu is used to program the process type for the initiating circuits. The maximum number o
FA-300 Series LCD Version Installation and Operation Manual43Command Menu-->FA-300 ConfigOpt ZoneThis menu is used to program the process type of t
Configuration 44Command Menu-->FA-300 ConfigInp Zone Label Use the keypad described below for entering a message. Note: Refer to How to Use the Ke
FA-300 Series LCD Version Installation and Operation Manual45Command Menu-->FA-300 ConfigOpt Zone LabelUse the keys in described below for entering
Configuration 462. Config Info (Command-Menu)Note: Refer to How to Use the Keypad to Program the FA-300 on page 39 for detailed instructions on makin
FA-300 Series LCD Version Installation and Operation Manual473. Set Time (Command-Menu)Note: Refer to How to Use the Keypad to Program the FA-300 on
Configuration 484. Set Password (Command-Menu)5. View Event Log (Command-Menu)The event log looks the same as the normal event queue. Pressing the “IN
FA-300 Series LCD Version Installation and Operation Manual496. Clear Event Log (Command-Menu)Note: Refer to How to Use the Keypad to Program the FA-
Configuration 507. Walk Test (Command-Menu)Walk-Test allows an installer to verify the initiating circuit wiring in a system. When walk test is select
FA-300 Series LCD Version Installation and Operation Manual518. i3 Loop Test (Command-Menu)The i3 maintenance test is designed to test the devices on
iiSynchronous Strobes... 34System Sensor’s i3
Configuration 529. Dialer Config (Command-Menu)The following illustration shows the dialer configuration menu. Each item in this menu is described bel
FA-300 Series LCD Version Installation and Operation Manual53Command Menu/Dialer Config/Account Info2.Account#1 Telephone Number[ 101 ]->DefaultUse
Configuration 54Command Menu-->Dialer ConfigTelephone LineNote: Refer to How to Use the Keypad to Program the FA-300 on page 39 for detailed instr
FA-300 Series LCD Version Installation and Operation Manual55Command Menu-->Dialer-ConfigReport OptionsNote: Refer to How to Use the Keypad to Pro
Configuration 56Command Menu-->Dialer-ConfigTime ParametersCommand Menu/Dialer-Config/Report Options6.Dialer operation mode[X] (U)DACT ->Default
FA-300 Series LCD Version Installation and Operation Manual57Command Menu-->Dialer-ConfigDialer Enable/DisableCommand Menu-->Dialer-ConfigRing D
Configuration 58Dialer Test MessagesThe following messages will display during the test processes of Lines #1 and #2. The messages that will appear de
FA-300 Series LCD Version Installation and Operation Manual5911. Bypass Det Ckt (Command-Menu)12. Bypass NAC Ckt (Command-Menu)13. Aux. Disconnect (Co
Configuration 6014. Exit (Command-Menu)Pressing “ENTER” after selecting “Exit” from the main menu will return the panel to normal LCD operation. Zone
FA-300 Series LCD Version Installation and Operation Manual61AC Power FailThe AC power fail trouble is generated when the power drops below the UL spe
FA-300 Series LCD Version Installation and Operation ManualiList of Figures and TablesFiguresFigure 1: Box dimensions, surface mount...
Configuration 62Remote AnnunciatorTroubles related to the annunciator can have two possibilities: either the main panel and annunciator failed to comm
FA-300 Series LCD Version Installation and Operation Manual63Supervised auxiliary supplyThe supervised auxiliary supply is supervised for shorts. When
Configuration 64If there is an open detected on the city tie output, the following trouble message is displayed:Note: The trouble code and info is for
FA-300 Series LCD Version Installation and Operation Manual65Appendix A: Compatible ReceiversThe dialers that are built into select models of the FA-3
Appendix B: Reporting66Appendix B: ReportingAdemco Contact-IDFA-300 Event Codes NNN-Refers to Sensor number for zone causing event.Event Description
FA-300 Series LCD Version Installation and Operation Manual67Security Industries Association SIA-DCSSIA protocol does not define indicating zone troub
Appendix C: Specifications68Appendix C: SpecificationsFA-300 Fire Alarm Control Panel (LCD) RM-312/306 Relay adder moduleDigital Signal Processor (DSP
FA-300 Series LCD Version Installation and Operation Manual69Appendix D: Power Supply and Battery Calculations (Selection Guide)Use the form below to
Warranty & Warning Information70Warranty & Warning InformationWarning Please Read Carefully Note to End Users: This equipment is subject to te
FA-300 Series LCD Version Installation and Operation Manual71of closed doors; and, smoke and heat detectors may not detect smoke or heat from fires on
List of Figures and Tablesii
Warranty & Warning Information72Limited Warranty Mircom Technologies Ltd. warrants the original purchaser that for a period of two years from the
FA-300 Series LCD Version Installation and Operation Manual73Out of Warranty Repairs Mircom Technologies Ltd. will at its option repair or replace out
Canada25 Interchange WayVaughan, ON L4K 5W3Tel: 905-660-4655 Fax: 905-660-4113© Mircom 2006Printed in CanadaSubject to change without prior noticewww.