FA-300 Series LCD Version Installation and Operation Manual
39
How to Use the Keypad to Program the FA-300
1. Press MENU to enter the command menu.
2. Select a Command Menu option by pressing ENTER. The corresponding submenu will display.
3. Use the up and down arrow buttons to scroll through the submenu.
4. Press ENTER to select a submenu option.
5. Use the left or right arrow buttons to select/unselect an option (selected = “X
”). Use the up and down arrows to
scroll through the different options.
6. Once you have made the correct selection, press ENTER to confirm the change. The display will return to the
submenu screen.
7. Press CANCEL to return to the previous menu.
Command Menu/FA-300 Config/Features/
1. Manual Signal Silence
[X] ENABLE->Default
[ ] DISABLE
Use this function to enable or
disable the SIGNAL SILENCE
operation from the front panel.
Command Menu/FA-300 Config/Features/
2.Fire Drill
[X] ENABLE ->Default
[ ] DISABLE
Use this function to enable or
disable the FIRE DRILL
operation.
Command Menu/FA-300 Config/Features/
3.Output Circuit Correlation
[X] DISABLE ->Def
[ ] ENABLE
If disabled, whatever correlation
is set in the correlation section
is effective. If enabled, all the
output circuits are correlated to
all the input circuits.
Command Menu/FA-300 Config/Features/
4.Waterflow/Sprinkler Retard
Operation
[X] DISABLE ->Def
[ ] ENABLE
If disabled, all the initiating
circuits configured as water flow
or sprinkler act as non-verified
alarms. If enabled, retard
operation is performed for
initiating circuits configured as
water flow or sprinkler.
(See Water flow Alarm and
Sprinkler Alarm description)
Command Menu/FA-300 Config/Features/
5.Aux. disconnect, disconnects
Aux Alarm relay and all correlated
relays
[ ] ENABLE
[X] DISABLE->Default
In the default mode this function
will disconnect the Auxiliary
Alarm Relay when selected by
Command Menu, Item 12 which
acts like an Aux. disconnect
switch.
If enabled, this function will
disconnect the Auxiliary Alarm
relay and
all correlated relays
when selected by Command
Menu, Item 12 which acts like
an Aux. disconnect switch.
Correlated relays include:
RM312/RM306 relays, SRM-
312 relays.
Manual Sig. Silence
[X] ENABLE
Fire Drill
[X] ENABLE
Opt. Ckt. Corr.
[X] DISABLE
Waterflow/Sprk. Retd
[X] DISABLE
Aux Dis Corr
[X] DISABLE