Configuration
50
7. Walk Test (Command-Menu)
Walk-Test allows an installer to verify the initiating circuit wiring in a system. When walk test is selected, the following
screen confirms the operation:
Press the “ENTER” key to activate the walk test and the “CANCEL” key to cancel the walk test. The next screen will
allow zones to be selected for walk test. Use the “UP” and “DOWN” keys to scroll through the zones and use the
“LEFT” or ‘RIGHT” keys to select a zone. Press the “ENTER” key when you are done with all the selections.
The walk test is now active (see illustration below)
The activation of any initiating circuit that has been selected for a walk test will cause the Audible Indicating Circuits
(not Strobes) to activate briefly for a number of short bursts corresponding to the selected circuit number. If the first
selected circuit is activated, the indication circuits will sound for one burst. If the second selected circuit is activated,
the indication circuits will sound for two bursts, and so on. This means that if, for example, circuits 1, 3 and 5 were
selected for the walk test, the indicating circuits would sound with one, two and three bursts respectively. The burst
interval is half a second ON and half a second OFF. After the sounding pattern has been sent to the indicating
circuits, the initiating circuit is reset and tested again. If it is still active (in alarm) the pattern will be re-sent. Trouble
on any initiating circuit selected for the walk test activates the indicating circuits continuously for five seconds.
Activation of a circuit will also cause the alarm count to increase while the trouble on the initiating circuit will cause
the trouble count to increase.
Alarm Verification and Water flow Alarm Retard Operations are disabled on circuits being walk tested. All circuits not
selected for the walk test continue to function normally. If a circuit was disconnected before the walk-test mode was
entered and is not selected for the walk-test, it remains disconnected while the walk test is active. Walk test
operation is disabled if the Fire Alarm Control Panel is in alarm or goes into alarm while the walk test is active.
Note: Refer to How to Use the Keypad to Program the FA-300 on page 39 for detailed instructions on
making menu selections.
Notes:
If a UDACT is used with the system, all walk-test events will be reported to the monitoring agency. The
monitoring agency should be instructed to ignore reported events during the walk-test.
IF THERE IS NO ACTIVITY FOR ONE HOUR, THE SYSTEM WILL RETURN TO NORMAL
OPERATION.
Perform the
walk test? Y
-WALK TEST ZONES-
[ ] Zone-1
-Walk test active-
Alarm:00 Trb:00