FA-300 Series LCD Version Installation and Operation Manual
41
Command Menu/FA-300 Config/Features/
13.Signal Isolators
[ ] ENABLE
[X] DISABLE ->Def
Enable this function only when
suite isolators are used (Canada
only)
Command Menu/FA-300 Config/Features/
14.Strobe Type
[X] NORMAL ->Default
[ ] MIRCOM
[ ] FARADY
[ ] WHEELOCK
[ ] GENTEX
[ ] SYSTEM SENSOR
Use this function to select the
manufacturer of the strobes
used in the system. The
selection is system-wide and
applies to all indicating circuits
configured as strobes. For
“NORMAL” strobes there is no
synchronization, while other
strobes are synchronized and
use manufacturer’s protocol to
synchronize the strobes.
Command Menu/FA-300 Config/Features/
15.Evacuation Code
[X] TEMPORAL->Def
[ ] CONTINOUS
[ ] MARCH TIME
[ ] CALIFORNIA
Use this function to set the rate
at which the indicating circuits
will sound.
Command Menu/FA-300 Config/Features/
16. Active EOL
[X] DISABLE->Default
[ ] ENABLE
Enable this function if using an
Active EOL. If ICAC-306 is
used, this function should be
enabled since the Class A
Converter has built in Active
EOL resistors.
Note: Refer to How to Use the Keypad to Program the FA-300 on page 39 for detailed
instructions on making menu selections.
Sig-Sil. Isolator
[X] DISABLE
Strobe Type
[X] NORMAL
Evacuation Code
[X] TEMPORAL
Active EOL
[X] DISABLE