Configuring a Card Access System Panel
Version 2.4 TX3 Configuration and Administrator Manual 125 (165)
LT-995 Copyright 2012
Panel label. Provide a name for the Panel.
Panel model. The application automatically retrieves the selected panel
model information. This field is read only.
Address. The drop down list displays the remaining available panel
addresses. From this list select the panel address. This field is disabled if
a connection is active. Ensure that this address matches the panel address.
3. Proceed with the rest of the configuration or click Send and Exit from
the Tool Bar to apply the settings and exit the session.
6.1.2 Setting the Card Access Panel
The application lets you set and define log reporting, facility code usage,
interlock access and daylight savings time.
The Card Access System supports both the 26 bit Wiegand and the 37 bit Mircom
proprietary card reader standards for each access point at the same time.
Interlock mode is typically used in a double door application to prevent
unauthorised access. During this mode the user presents the card at both doors.
The second door unlocks after presenting the card, if the first door is locked and
closed.
Cards contain facility code and card number information. The Card Access
System is configurable to grant access on the basis of one of the following:
• facility code only
• card number only
• facility code and card number