FA-262 Installation & Operator’s Manual
7
2.8 Calculation for Standby Battery Requirement
Step Device
Current per
device (mA)
Number
of device
Total
Standby
Current (mA)
Total Alarm
Current
(mA)
1 FA-262
Standby:
90
x1 =
90
Alarm:
365
x1 =
2
Zone 1
Standby: x =
Alarm: 69 x 1 = 69
Zone 2
Standby: x =
Alarm: 69 x 1 =
3
NAC 1 Alarm: x
NAC 2 Alarm: x
4
RTI-265
Standby: 15 x
Alarm: 15 x
RAM-265
Standby: 15 x
Alarm: 25 x
UDACT-286
Standby: 45 x
Alarm: 60 x
RM-263
Standby: 0 x =
Alarm: 24 x
5
AUX+
Standby: x =
Alarm: x =
6
Total ‘standby’ and ‘alarm’ current: mA mA
7
Divide ‘standby’ mA and ‘alarm’ mA by 1000: Amp Amp
8
Select ‘standby’ time required (24 or 60 Hr.): Hr.
9
Standby Amp-Hr. - multiply 8 × 7 = (Amps × Hr.): Amp-Hr.
10 Select ‘alarm’ time required
(0.08 or 0.5):
Hr.
11
Alarm Amp-Hr. - multiply 7 × 10 = (Amps × Hr.): Amp-Hr.
12
Total Amp-Hr = standby Amp-Hr (9) + alarm Amp-Hr. (11): Amp-Hr.
13
Multiply the total Amp-Hr. by the safety margin: 1.20
14
Total battery Amp-Hr required to support the system:
Amp-Hr.
Note: Select a battery with an Amp-Hr. rating that is equal to or larger than the calculated minimum Amp-
Hr. battery required.