Mircom FA-300 Series Manuel d'utilisateur Page 2

  • Télécharger
  • Ajouter à mon manuel
  • Imprimer
  • Page
    / 6
  • Table des matières
  • MARQUE LIVRES
  • Noté. / 5. Basé sur avis des utilisateurs
Vue de la page 1
Initiating Circuits
The FA-300 Series panels are equipped with Class
“B” (Style “B”) initiating circuits. The initiating circuits
may be congured as Class “A” (Style “D”) using an
ICAC-306 Class “A” converter adder module.
Each Initiating circuit may be congured for one of
the following modes of operation:
• Alarm (Without smoke detector verication)
• Veried Alarm (With smoke detector
verication)
• Waterow Alarm (Water ow sensors)
• Sprinkler Alarm (Sprinkler ow sensors)
• Latching Supervisory
• Non-Latching Supervisory
• Monitor (non-latching input used mainly for
correlating to a relay circuit)
• Trouble-Only (for monitoring a trouble condition
from an external device)
Features
CAT. 5662
page 2 of 6
NOT TO BE USED FOR INSTALLATION PURPOSES.
UDACT/Digital Communicator
The FA-300 Series panels are equipped with a fully
integrated UDACT/Digital Communicator which allows
for the reporting of events to a monitoring facility. The
UDACT/Digital Communicator can be congured for
single or dual line operation and uses the Security
Industry Association (SIA) and Ademco Contact ID
protocols. The UDACT/Digital Communicator is
congured via the main display and keypad on the
main panel.
In addition to its reporting functions, the integrated
UDACT/Digital Communicator can be used to connect
to the FA-300 panel from remote computers for
uploading and downloading of conguration data. It
also allows for the viewing of the event history logs.
The FA-300 series panels have two event history
logs comprised of a 200 event alarm log for alarm
related events and a 200 event general log for all
other events.
The integrated UDACT/Digital Communicator can
be congured for either DACT or UDACT operation.
In DACT mode the Digital Communicator reports
common alarm, trouble and supervisory information.
In UDACT mode the Digital Communicator reports
point specic information.
Indicating Circuits
The FA-300 Series panels are equipped with
equipped with Class “B” (Style “B”) indicating circuits.
The indicating circuits may be congured as Class
“A” (Style “Z”) using an OCAC-304 or OCAC-302
Class “A” signal converter adder module. The audible
signals may be congured for Steady, Temporal Code,
California Code and March Time.
Each of the indicating circuits may be congured for
one of the following modes of operation:
• Silenceable Signal
• Non-Silenceable Signal
• Silenceable Strobe
• Non-Sileneceable Strobe
The FA-300 has built-in sync protocols for the
following strobe manufacturers; Mircom, Amseco,
System Sensor, Gentex, Faraday and Wheelock.
i3 Series Protocol
The FA-300 Series panels have the i3 Series protocol
built-in. The panels support the two-wire i3 Series
smoke detectors (2W-B/2WT-B). These i3 series
detectors communicate with the FA-300 to provide
the following status information:
Open circuit trouble
This trouble indicates that loop is broken.
Communication trouble
This trouble indicates that there is a fault in the line or
the line is too noisy, the panel cannot communicate
with the devices.
Dirty device
This trouble indicates that one or more device on the
i3 zone is dirty.
Out of sensitivity
This trouble indicates that one or more device on the
i3 zone is out of sensitivity range and cannot detect
an alarm condition.
Freeze trouble
This trouble indicates that a device on the i3 zone has
detected a freeze condition, e.g. the temperature is
below 41°F / 5 °C (available only on model 2WT-B).
The built-in protocol removes the need for the 2W-
MOD Maintenance Module.